Vertiv Liebert EXS UPS (Tower)
10kVA/10kW
Nominal Power (kVA) 10
Input Parameters
Input Voltage (V) 380/400/415 VAC 3-Phase,
(three-phase + N + PE)
Input voltage range without battery discharge (V)
173 to 498
Frequency (Hz) 50/60
Input frequency range (Hz) 40 to 70
Input Power Factor (kW/kVA) 0.99
Current THD at Full Linear Load ≤ 3%
Bypass voltage tolerance (%)
selectable from +20 to -40
Bypass frequency tolerance (%) ±20
(±10 selectable)
Battery
Battery Blocks Per String 24-40
Battery Charger Max. Power (A) 13
Output
Output Voltage (V)
"380/400/415 (three-phase + N + PE) or
220/230/240 (single-phase + N + PE)"
Maximum active power (kW) 10
Frequency (Hz) 50/60
THDv at full linear load (%) 2
Overload Capacity @ at 25 °C
"105% for 60 min; 125% for 5 min;
150% for 1 min; >150% for 200ms"
Efficiency
Online Mode Efficiency Up to 96.2%
ECO Mode Efficiency Up to 99%
Dimensions and Weight
"Dimensions (W x D x H) in mm"
"335 x 650 x 1300 (standard version)
577 x 650 x 1300 (extended version)"
Net/Shipping weight (excluding battery) kg
85/115 (standard version)
Net/Shipping weight (including 2*32 batteries) kg
285/315 (standard version)
General
Operating Temperature (°C) 0 ~ 50
Nosie at 1 m (dBA) <58
Protection level IEC (60529)
IP20 (IP31 is optional)
Maximum altitude
1500 m without derating (max. 3000 m)
General and Safety Requirements for UPS
EN/IEC/AS 62040-1
EMC Requirements for UPS EN/IEC/AS 62040-2
"UPS Classification According to IEC 62040-3"
VFI-SS-111
"Central Power Supply Systems (CPSS) applications*"
EN 50171
Rail applications
"EN 50121-1 EN 50121-5"
1 Yr On Site Replacement Warranty

Capslock Co.,Ltd.
Liebert Vertiv UPS 3 Phase is ideal for businesses needing stable and efficient power supply. It handles heavy loads well and protects against power outages or surges. It has a long lifespan, real-time monitoring software, and reliable after-sales support. This makes it perfect for data centers and organizations that require high reliability.
Vertiv Liebert EXS UPS (Tower)
20kVA/20kW
Nominal Power (kVA) 20
Input Parameters
Input Voltage (V) 380/400/415 VAC 3-Phase,
(three-phase + N + PE)
Input voltage range without battery discharge (V)
173 to 498
Frequency (Hz) 50/60
Input frequency range (Hz) 40 to 70
Input Power Factor (kW/kVA) 0.99
Current THD at Full Linear Load ≤ 3%
Bypass voltage tolerance (%)
selectable from +20 to -40
Bypass frequency tolerance (%) ±20
(±10 selectable)
Battery
Battery Blocks Per String 24-40
Battery Charger Max. Power (A) 13
Output
Output Voltage (V)
"380/400/415 (three-phase + N + PE) or
220/230/240 (single-phase + N + PE)"
Maximum active power (kW) 20
Frequency (Hz) 50/60
THDv at full linear load (%) 2
Overload Capacity @ at 25 °C
"105% for 60 min; 125% for 5 min;
150% for 1 min; >150% for 200ms"
Efficiency
Online Mode Efficiency Up to 96.2%
ECO Mode Efficiency Up to 99%
Dimensions and Weight
"Dimensions (W x D x H) in mm"
"335 x 650 x 1300 (standard version)
577 x 650 x 1300 (extended version)"
Net/Shipping weight (excluding battery) kg
85/115 (standard version)
Net/Shipping weight (including 2*32 batteries) kg
285/315 (standard version)
General
Operating Temperature (°C) 0 ~ 50
Nosie at 1 m (dBA) <58
Protection level IEC (60529)
IP20 (IP31 is optional)
Maximum altitude
1500 m without derating (max. 3000 m)
General and Safety Requirements for UPS
EN/IEC/AS 62040-1
EMC Requirements for UPS EN/IEC/AS 62040-2
"UPS Classification According to IEC 62040-3"
VFI-SS-111
"Central Power Supply Systems (CPSS) applications*"
EN 50171
Rail applications
"EN 50121-1 EN 50121-5"
1 Yr On Site Replacement Warranty
Vertiv Liebert EXS UPS (Tower)
30kVA/30kW
Nominal Power (kVA) 30
Input Parameters
Input Voltage (V) 380/400/415 VAC 3-Phase,
(three-phase + N + PE)
Input voltage range without battery discharge (V)
228 to 475
Frequency (Hz) 50/60
Input frequency range (Hz) 40 to 70
Input Power Factor (kW/kVA) 0.99
Current THD at Full Linear Load ≤ 3%
Bypass voltage tolerance (%)
selectable from +20 to -40
Bypass frequency tolerance (%) ±20
(±10 selectable)
Battery
Battery Blocks Per String 26-40
Battery Charger Max. Power (A) 12.5
Output
Output Voltage (V)
380/400/415 (three-phase + N + PE)
Maximum active power (kW) 30
Frequency (Hz) 50/60
THDv at full linear load (%) 2
Overload Capacity @ at 25 °C
"105% for 60 min; 125% for 5 min;
150% for 1 min; >150% for 200ms"
Efficiency
Online Mode Efficiency Up to 96.2%
ECO Mode Efficiency Up to 99%
Dimensions and Weight
"Dimensions (W x D x H) in mm" 440 x 750 x 1600
Net/Shipping weight (excluding battery) kg 200/250
Net/Shipping weight (including 2*32 batteries) kg 600/650
General
Operating Temperature (°C) 0 ~ 40
Nosie at 1 m (dBA) <58
Protection level IEC (60529)
IP20 (IP31 is optional)
Maximum altitude
1500 m without derating (max. 3000 m)
General and Safety Requirements for UPS
EN/IEC/AS 62040-1
EMC Requirements for UPS EN/IEC/AS 62040-2
"UPS Classification According to IEC 62040-3"
VFI-SS-111
"Central Power Supply Systems (CPSS) applications*"
EN 50171
Rail applications
"EN 50121-1 EN 50121-5"
1 Yr On Site Replacement Warranty
Vertiv Liebert EXS UPS (Tower)
40kVA/40kW
Nominal Power (kVA) 40
Input Parameters
Input Voltage (V) 380/400/415 VAC 3-Phase,
(three-phase + N + PE)
Input voltage range without battery discharge (V)
228 to 475
Frequency (Hz) 50/60
Input frequency range (Hz) 40 to 70
Input Power Factor (kW/kVA) 0.99
Current THD at Full Linear Load ≤ 3%
Bypass voltage tolerance (%)
selectable from +20 to -40
Bypass frequency tolerance (%) ±20
(±10 selectable)
Battery
Battery Blocks Per String 26-40
Battery Charger Max. Power (A) 12.5
Output
Output Voltage (V)
380/400/415 (three-phase + N + PE)
Maximum active power (kW) 40
Frequency (Hz) 50/60
THDv at full linear load (%) 2
Overload Capacity @ at 25 °C
"105% for 60 min; 125% for 5 min;
150% for 1 min; >150% for 200ms"
Efficiency
Online Mode Efficiency Up to 96.2%
ECO Mode Efficiency Up to 99%
Dimensions and Weight
"Dimensions (W x D x H) in mm" 441 x 750 x 1600
Net/Shipping weight (excluding battery) kg 200/250
Net/Shipping weight (including 2*32 batteries) kg 600/650
General
Operating Temperature (°C) 0 ~ 40
Nosie at 1 m (dBA) <58
Protection level IEC (60529)
IP20 (IP31 is optional)
Maximum altitude
1500 m without derating (max. 3000 m)
General and Safety Requirements for UPS
EN/IEC/AS 62040-1
EMC Requirements for UPS EN/IEC/AS 62040-2
"UPS Classification According to IEC 62040-3"
VFI-SS-111
"Central Power Supply Systems (CPSS) applications*"
EN 50171
Rail applications
"EN 50121-1 EN 50121-5"
1 Yr On Site Replacement Warranty
Vertiv Liebert EXS UPS (Tower)
60kVA/60kW
Nominal Power (kVA) 60
Input Parameters
Input Voltage (V) 380/400/415 VAC 3-Phase,
(three-phase + N + PE)
Input voltage range without battery discharge (V)
228 to 475
Frequency (Hz) 50/60
Input frequency range (Hz) 40 to 70
Input Power Factor (kW/kVA) 0.99
Current THD at Full Linear Load ≤ 3%
Bypass voltage tolerance (%)
selectable from +20 to -40
Bypass frequency tolerance (%) ±20
(±10 selectable)
Battery
Battery Blocks Per String 26-40
Battery Charger Max. Power (A) 25
Output
Output Voltage (V)
380/400/415 (three-phase + N + PE)
Maximum active power (kW) 60
Frequency (Hz) 50/60
THDv at full linear load (%) 2
Overload Capacity @ at 25 °C
"105% for 60 min; 125% for 5 min;
150% for 1 min; >150% for 200ms"
Efficiency
Online Mode Efficiency Up to 96.2%
ECO Mode Efficiency Up to 99%
Dimensions and Weight
"Dimensions (W x D x H) in mm" 600 x 850 x 1600
Net/Shipping weight (excluding battery) kg 215/265
Net/Shipping weight (including 2*32 batteries) kg 700/750
General
Operating Temperature (°C) 0 ~ 40
Nosie at 1 m (dBA) <60
Protection level IEC (60529)
IP20 (IP31 is optional)
Maximum altitude
1500 m without derating (max. 3000 m)
General and Safety Requirements for UPS
EN/IEC/AS 62040-1
EMC Requirements for UPS EN/IEC/AS 62040-2
"UPS Classification According to IEC 62040-3"
VFI-SS-111
"Central Power Supply Systems (CPSS) applications*"
EN 50171
Rail applications
"EN 50121-1 EN 50121-5"
1 Yr On Site Replacement Warranty
Vertiv Liebert EXS UPS (Tower)
80kVA/80kW
Nominal Power (kVA) 80
Input Parameters
Input Voltage (V) 380/400/415 VAC 3-Phase,
(three-phase + N + PE)
Input voltage range without battery discharge (V)
228 to 475
Frequency (Hz) 50/60
Input frequency range (Hz) 40 to 70
Input Power Factor (kW/kVA) 0.99
Current THD at Full Linear Load ≤ 3%
Bypass voltage tolerance (%)
selectable from +20 to -40
Bypass frequency tolerance (%) ±20
(±10 selectable)
Battery
Battery Blocks Per String 26-40
Battery Charger Max. Power (A) 25
Output
Output Voltage (V)
380/400/415 (three-phase + N + PE)
Maximum active power (kW) 80
Frequency (Hz) 50/60
THDv at full linear load (%) 2
Overload Capacity @ at 25 °C
"105% for 60 min; 125% for 5 min;
150% for 1 min; >150% for 200ms"
Efficiency
Online Mode Efficiency Up to 96.2%
ECO Mode Efficiency Up to 99%
Dimensions and Weight
"Dimensions (W x D x H) in mm" 601 x 850 x 1600
Net/Shipping weight (excluding battery) kg 230/270
Net/Shipping weight (including 2*32 batteries) kg N/A
General
Operating Temperature (°C) 0 ~ 40
Nosie at 1 m (dBA) <60
Protection level IEC (60529)
IP20 (IP31 is optional)
Maximum altitude
1500 m without derating (max. 3000 m)
General and Safety Requirements for UPS
EN/IEC/AS 62040-1
EMC Requirements for UPS EN/IEC/AS 62040-2
"UPS Classification According to IEC 62040-3"
VFI-SS-111
"Central Power Supply Systems (CPSS) applications*"
EN 50171
Rail applications
"EN 50121-1 EN 50121-5"
1 Yr On Site Replacement Warranty
The Liebert EXS UPS
is a compact three-phase power solution that delivers simplicity, reliability, and high efficiency. It features an integrated maintenance bypass, advanced monitoring, and flexible output and battery runtime options. Its transformer-free, on-line design ensures robust protection while reducing installation costs. With a small footprint and high power capacity, it provides a reliable and economical UPS solution.
All rights reserved to Capslock Company Limited- 2022
ติดต่อเรา
บริษัท แค็พซล็อค จำกัด
50 ซอยงามวงศ์วาน 23 ถนนงามวงศ์วาน
ตำบลบางเขน อำเภอบางเขน จังหวัดนนทบุรี 11000
โทร 0 2952 7823 (auto) แฟ็กซ์ 0 2952 7423
Email : info@capslockthai.com
Line ID : @thailandups
เลขประจำตัวผู้เสียภาษี 0125546012411
เวลาทำการ จันทร์ - ศุกร์ 8.30 - 17.30 น.
Contact us
Capslock Company Limited
50 Soi Ngamwongwan 23 Ngamwongwan Rd
Bangkhen Subdistrict Muang District Nonthaburi 11000
Tel 0 2952 7823 (auto) Fax 0 2952 7423
Email : info@capslockthai.com
Line ID : @thailandups
TAX ID 0125546012411
Office hours : Monday - Friday 8.30 am - 5.30 pm
ธนาคารสำหรับโอนเงินค่าสินค้า/ Bank ( payment transfer)
ชื่อบัญชี / account name บจ แค็พซล็อค / Capslock Co.,Ltd
ธนาคารกรุงศรีอยุธยา สาขาเซ็นทรัล รัตนาธิเบศร์
Krungsri Bank, Central Rattanathibet Branch, Saving account
เลขที่บัญชี /Account number 241 1 26526 3
ธนาคารกสิกรไทย สาขาโรบินสัน ศรีสมาน - ออมทรัพย์
Kasikorn Bank, Ronbinson Srisaman Branch, Saving account
เลขที่บัญชี /Account number 039 2 79050 0
ธนาคารกรุงเทพ สาขาเดอะมอลล์ งามวงศ์วาน - ออมทรัพย์
Bangkok Bank, The mall Ngamwongwan Branch, Saving account
เลขที่บัญชี /Account number 088 0 89859 8
ใบทะเบียนภาษีมูลค่าเพิ่ม (ภ.พ.20)
แผนที่
หมายเหตุ
- ภาพใช้แสดงเป็นตัวอย่างเท่านั้น
- ราคาดังกล่าวยังไม่รวมภาษีมูลค่าเพิ่ม
- ราคาอาจมีการเปลี่ยนแปลงโดยไม่ต้องแจ้งให้ทราบล่วงหน้า
- ทางร้านขอสงวนสิทธิ์ในความรับผิดชอบใดๆ อันเนื่องจาก
ข้อผิดพลาดในการพิมพ์ (ผิด/ตก) ไม่ว่ากรณีใดๆ ก็ตาม
Liebert EXS: 10KVA/10KW, 400V, 3x3 or 3x1, without internal battery Support up to
2 battery strings
P/N 01201891
Liebert EXS: 10KVA/10KW, 400V, 3x3 or 3x1, with sidecar, without internal battery Support up to
4 battery strings
P/N 01201892
Liebert EXS: 20KVA/20KW, 400V, 3x3 or 3x1, without internal battery Support up to 2 battery strings P/N 01201830
Liebert EXS: 20KVA/20KW, 400V, 3x3 or 3x1, with sidecar, without internal battery Support up to 4 battery strings P/N 01201831
Liebert EXS: 30KVA/30KW, 400V, 3x3, without internal battery
On-Line Double Conversion 3x3 (output pf 1.0)
Support up to 4 battery strings
P/N 01201915
Liebert EXS: 40KVA/40KW, 400V, 3x3, without internal battery
On-Line Double Conversion 3x3 (output pf 1.0)
Support up to 4 battery strings
P/N 01201821
Liebert EXS: 60KVA/60KW, 400V,
3x3, without internal battery
On-Line Double Conversion 3x3
(output pf 1.0)
Liebert EXS: 80KVA/80KW, 400V,
3x3, without internal battery
On-Line Double Conversion 3x3
(output pf 1.0)
ติดต่อสอบถามเพิ่มเติม
ติดต่อสอบถามเพิ่มเติม
ติดต่อสอบถามเพิ่มเติม
ติดต่อสอบถามเพิ่มเติม
ติดต่อสอบถามเพิ่มเติม
ติดต่อสอบถามเพิ่มเติม
Vertiv™ Liebert® UPS 3 PHASE - EXS UPS Series